Vertiv Liebert GXT MT+ Series systems is true double conversion online UPS systems designed to provide with a capacity of 2 kVA. Liebert GXT MT+ units feature total isolation of the load from the mains - isolating input and output sections, and making the systems ideal for Data Networks / Small Data Centers /VOIP Applications application. The units support hot standby configuration, making them suited for critical applications like banks. Features: • IGBT Based Rectifier • True Online Double Conversion with DSP Control Technology for High Performance and Reliability. • New Graphical LCD Display Provides UPS Data, Alarms and Helps in faults diagnostics and trouble shooting. • Double Conversion Efficiency upto 90%. • Active Input Power Factor Correction 0.99. • Output Power Factor: 0.8 • Wide Input Voltage window (110 - 280 Vac) for Indian Environmental Condition and for Optimized Battery Performance. • Configurable Output Voltage (200/208/220/230/240 Vac.) • Generator Compatible with Wide Input Frequency Range (40 Hz-70 Hz). • 4 Stage Extendable Charging Design for optimized Battery Performance. • Adjustable Battery Charging Current 1/2/4/6 Amps according to Battery Capacity and Rating. • 50/60 Hz Automatic Frequency Converter Mode. • Intelligent Monitoring with Standard RS232/USB Port Plus Slot Available for RS485/Dry Contact/SNMP Card. • Inbuilt OVCD. Best Suited For: • Education, Data Center/Colocation/Hosting, Construction and Engineering, Government, Healthcare, Manufacturing
| MODEL | GXT MT + CX 2 kVA |
| PHASE | 1 phase in / 1 phase out |
| CAPACITY (kVA) | 2 kVA |
| CAPACITY (kW) | 1.60 kW |
| INPUT | |
| Nominal Voltage | 230 Vac |
| Voltage Range - Low Line Loss | 110 VAC ± 3% at 50% Load / 176 VAC ± 3% at 100% Load |
| Voltage Range - Low Line Comeback | 120 VAC ± 3% at 50% Load / 186 VAC ± 3% at 100% Load |
| Voltage Range - High Line Loss | 280 VAC ± 3% |
| Voltage Range - High Line Comeback | 270 VAC ± 3% |
| Frequency Range | 40 Hz ~ 70 Hz |
| Power Factor | 0.99 @ 100% load |
| OUTPUT | |
| Nominal Voltage | 208/220/230/240VAC |
| AC Voltage Regulation | ± 1% |
| Frequency Range (Synchronized Range) | 46Hz ~ 54 Hz or 56Hz ~ 64 Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | 3 % THD (Linear Load), 7 % THD (Non-linear Load) |
| Transfer Time - Bypass to Inverter (Line mode) | Zero |
| Transfer Time - Inverter to Bypass (Line mode) | 4 ms (Typical) |
| Waveform (Batt. Mode) | Pure Sinewave |
| EFFICIENCY on AC to AC mode@ 100% load. | 88% |
| Inbuilt Isolation Transformer | No |
| BATTERY | |
| Battery Type | 12V/ 9 AH |
| Numbers | 4 |
| Typical Recharge Time | 4 hours recover to 90% capacity |
| Charging Current (max.) | 1.0 A |
| Charging Voltage | 54.7 VDC ±1% |
| INDICATORS | |
| LCD Panel | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
| ALARM | |
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Countinously sounding |
| PHYSICAL | |
| Dimension, D x W x H (mm) | 397 x145 x220 |
| Net Weight (kgs) | 17 |
| ENVIRONMENT | |
| Operation Humidity and Temperature | 20-90 % RH @ 0- 45°C (non-condensing) |
| Noise Level | Less than 50dBA @ 1 Meter |
| MANAGEMENT | |
| Smart RS-232/USB | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
| T&C | * Derate to 80% of capacity in Frequency converter mode,the output voltage is adjusted to 100/200/208VAC and the ambient temperature during 45°C to 50°C / * * Product specifications are subject to change without further notice |