Liebert GXT MTX+ 6 kVA is a full featured Transformer based UPS designed to offer compact efficient and reliable power thirsty modern electronic gadgets. The Liebert GXT MTX+ 6 kVA is compact UPS System with best-in-class Online UPS technology suited for critical applications such as IT & Communication Equipments, VolP, Small/Medium Data Centre, Server Rooms, ATMs etc. Features & Benefits: • Rating: 6 kVA / 4.80 kW • Model: GXT MTX+ 6 kVA • Phase: 1 Phase IN / 1 Phase OUT • I/P Voltage: 230 Vac (1 Ph+ N) • O/P Voltage: 208**/220/230/240 VAC • Inbuilt Isolation Transformer • IGBT Based Rectifier. • True Online Double Conversion with DSP Control Technology for High Performance and Reliability. • New Graphical LCD Display Provides UPS Data, Alarms and Helps in faults diagnostics and troubleshooting. • Double Conversion Efficiency upto 84%. • Active Input Power Factor Correction 0.99. • Output Power Factor: 0.8 • Wide Input Voltage window (110 — 300 Vac) for Indian Environmental Condition and for Optimized Battery Performance. • Adjustable Battery Configuration from 16*/18*/20 pcs and Digital battery Charger with Adjustable Charging Current (0.5 Amps to 6 Amps) Via LCD Display. • 3 Stage Extendable Charging Design for the Optimized Battery Performance. • CE and ROHS Compliance.
| Isolation Transformer | Inbuilt |
| Technical Specifications | |
| Model | GXT MTX+ 6 kVA |
| Capacity (kVA) | 6 kVA |
| Capacity (kW) | 4.80 kW |
| Phase | 1 Phase IN - 1 Phase OUT |
| Input | |
| Voltage Range | |
| Low Line Loss | 110 VAC ± 3% at 50% Load / 160 VAC ± 3% at 100% Load |
| Low Line Comeback | Low Line Loss Voltage +10V |
| High Line Loss | 300 VAC ± 3% |
| High Line Comeback | High Line Loss Voltage - 10V |
| Frequency Range | 46Hz ~ 54Hz @ 50Hz system / 56Hz ~ 64Hz @ 60Hz system |
| Phase | Single phase with ground |
| Power Factor | ≥ 0.99 @ 100% load |
| Output | |
| Output Voltage | 220/230/240VAC |
| Ac Voltage Regulation | ± 1% |
| Frequency Range (Synchronized Range) | 46 Hz ~ 54 Hz @ 50Hz system or 56 Hz ~ 64 Hz @ 60Hz system |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Power Factor | 0.8 |
| Overload | |
| AC Mode | 100% ~ 105%: 10min, 105% ~ 125%: 1min, >125% : 1sec |
| Battery Mode | 100% ~ 105%: 30sec, 105% ~ 125%: 10sec, >125% : 1sec |
| Current Crest Ratio | 3:1 max |
| Harmonic Distortion | 3 % @ 100% Linear Load : 7% @100% Non-Linear Load |
| Transfer Time | |
| Line to Battery | 0 ms |
| Inverter to Bypass | 0 ms |
| Configuration | Standalone / Hot-Standby |
| AC Mode | >84% |
| Battery Mode | >83% |
| Battery | |
| Type | Lead acid/Tubular/Li-ion |
| Numbers | 16-20 Derating capacity = original real power capacity X N/20 |
| Charging Current | Default: 4 A ± 10% / Max.: 6A ± 10% (settable) |
| Charging Voltage | 13.65 V ±1% |
| Physical | |
| Dimension, D x W x H (mm) | 369x190x630 |
| Net Weight (kgs) | 72 |
| Environment | |
| Operation Temperature | 0 ~ 40C (battery life cycle will be shorten when temperature is above 25C) |
| Operation Humidity | <95 % and non-condensing |
| Operation Altitiude | <1000m |
| Acoustic Noise Level | Less than 65dBA @ 1 Meter |
| Management | |
| Smart Rs-232/Usb | Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC |
| Optional Snmp | Power management from SNMP manager and web browser |
| T&C | |
| Warranty | 1 Year on UPS |
| Vertiv T&C | * Product specifications are subject to change without further notice **Derate capacity to 90% of capacity when the output voltage is adjusted to 208VAC ** *When using batteries from 16-19, the unit will be de-rate according to formula ; P= Prating X N/20 |