Description

Vertiv Liebert GXT MT+ Series system is true double conversion Online UPS systems designed to provide with a capacity of 3 kVA. Liebert GXT MT+ units feature total isolation of the load from the mains - isolating input and output sections, and making the systems ideal for Data Networks / Small Data Centers /VOIP Applications application. The units support hot standby configuration, making them suited for critical applications like banks. Features: • IGBT Based Rectifier • True Online Double Conversion with DSP Control Technology for High Performance and Reliability. • New Graphical LCD Display Provides UPS Data, Alarms and Helps in faults diagnostics and trouble shooting. • Double Conversion Efficiency upto 90%. • Active Input Power Factor Correction 0.99. • Output Power Factor: 0.8 • Wide Input Voltage window (110 - 280 Vac) for Indian Environmental Condition and for Optimized Battery Performance. • Configurable Output Voltage (200/208/220/230/240 Vac.) • Generator Compatible with Wide Input Frequency Range (40 Hz-70 Hz). • 4 Stage Extendable Charging Design for optimized Battery Performance. • Adjustable Battery Charging Current 1/2/4/6 Amps according to Battery Capacity and Rating. • 50/60 Hz Automatic Frequency Converter Mode. • Intelligent Monitoring with Standard RS232/USB Port Plus Slot Available for RS485/Dry Contact/SNMP Card. • Inbuilt OVCD. Best Suited For: • Education, Data Center/Colocation/Hosting, Construction and Engineering, Government, Healthcare, Manufacturing

MODEL GXT MT + CX 3 kVA LB
PHASE 1 phase in / 1 phase out
CAPACITY (kVA) 3 kVA
CAPACITY (kW) 2.40 kW
INPUT
Nominal Voltage 230 Vac
Voltage Range - Low Line Loss 110 VAC ± 3% at 50% Load / 176 VAC ± 3% at 100% Load
Voltage Range - Low Line Comeback 120 VAC ± 3% at 50% Load / 186 VAC ± 3% at 100% Load
Voltage Range - High Line Loss 280 VAC ± 3%
Voltage Range - High Line Comeback 270 VAC ± 3%
Frequency Range 40 Hz ~ 70 Hz
Power Factor  0.99 @ 100% load
OUTPUT
Nominal Voltage 208/220/230/240VAC
AC Voltage Regulation ± 1%
Frequency Range (Synchronized Range) 46Hz ~ 54 Hz or 56Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion  3 % THD (Linear Load),  7 % THD (Non-linear Load)
Transfer Time - Bypass to Inverter (Line mode) Zero
Transfer Time - Inverter to Bypass (Line mode) 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
EFFICIENCY on AC to AC mode@ 100% load. 90%
Inbuilt Isolation Transformer No
BATTERY
Battery Type Depending on the capacity of external batteries
Numbers 6
Charging Current 1.0A/2.0A/4.00.0A, 6.0A default
Float Charging Voltage "82.1 VDC *1%
INDICATORS
LCD Panel UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions
ALARM
Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Countinously sounding
PHYSICAL
Dimension, D x W x H (mm) 397 x145 x220
Net Weight (kgs) 7.4
ENVIRONMENT
Operation Humidity and Temperature 20-90 % RH @ 0- 45°C (non-condensing)
Noise Level Less than 50dBA @ 1 Meter
MANAGEMENT
Smart RS-232/USB Supports Windows® 2000/2003/XP/Vista/2008, Windows® 7, Linux, Unix, and MAC
Optional SNMP Power management from SNMP manager and web browser
T&C
Warranty 2 Years on UPS
OEM T&C * Derate to 80% of capacity in Frequency converter mode,the output voltage is adjusted to 100/200/208VAC and the ambient temperature during 45°C to 50°C / * * Product specifications are subject to change without further notice.