In today's dynamic world, it is not enough for enterprises to have basic power protection. With digital trends constantly emerging and transforming the way you do business, business continuity is even more vital. You simply cannot afford downtime in your critical system or waste time recovering these systems after a disruption. What you need is a robust, high-speed, reliable UPS system, which offers perennial, round-the-clock protection to diverse application needs. Liebert ITA2 offers best-in-class efficiency of up to 96.3% over a wide range of load conditions, resulting in significant OPEX cost savings. ITA2 integrated Smart Sleep technology in ECO mode provides a superlative efficiency of up to 99%. Features & Benefits: • Rating: 6 kVA/kW • Model: ITA2 (6 kVA) • Phase: 1 Phase IN / 1 Phase OUT • I/P Voltage: 220/230/240VAC 1-Phase, 2 Wire • O/P Voltage: 220/230/240 (1-phase) • Output Power Factor: Unity (1) i.e. kVA=kW • IGBT based Double conversion PWM based online UPS • Liebert ITA2 offers best-in-class efficiency of up to 96.5% in double conversion mode over a wide range of load conditions, resulting in significant OPEX cost savings. • Robust structure with cutting edge channelized airflow design • Wide input voltage range, making it immune to grid interference • Rack-tower design for installation flexibility • Able to deliver both three-phase and single-phase output • 0.99 input power factor for better grid or generator compatibility • Powerful charging capability for minimum battery recharging time • Programmable output outlets/terminals with cascade protection to protect key devices during heavy load • Integrated Ethernet port with HTTP protocol compatibility and streamlined remote monitoring • Easy to install, repair, and maintain • Compliance with seismic conduction and vehicle carrying test • Gravity sense LCD display • Power-Factor Correction • Lightning and Surge Protection • Wide Input Voltage Window • Turnkey dust-resistant design with ability to operate under high ambient temperature of up to 50ºC
| Higher Output Power Factor | Unity Power Factor |
| Technical Specifications | |
| Model | ITA- 06k00AL1102P00 / ITA- 06k00AE1102P00 |
| Phase | 1 Phase IN - 1 Phase OUT |
| Nominal Input Voltage (V) | 220/230/240VAC 1-Phase, 2 Wire |
| Input Voltage Range (V) | 176-288VAC at full load; 100-176VAC at linear derating; 100VAC at half load |
| Nominal Input Frequency (Hz) | 50/60 |
| Input Frequency Range (Hz) | 40-70 |
| Input Power Factor (kW/kVA)* | 0.99 |
| Current THD at full linear load (THDi%)* | <3 |
| Battery | |
| Battery Blocks Per String | 12*, 16, 20 |
| Battery Charger Max. Power (A) | = 5A (Long backup model) / = 2A (Standard model) |
| Battery Option | P/C : ITA-BCI0020K01 ( built-in battery module of 16 block X 12V X 9AH) Battery cabinet Dimensions in rack arrangement - 430(W) x 739(D) x 85(H) |
| Output | |
| Nominal Output Voltage (V) | 220/230/240 (1-phase) |
| Nominal Output Frequency (Hz) | 50/60 |
| Rated Power Factor (kW/kVA) | Unity |
| Voltage Harmonic Distortion (%) | <2% for Linear loads & <5% for Non-linear loads |
| Overload Capacity | At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms |
| Crest Factor | 3:1 |
| Online Mode Efficiency | Up to 95.5% |
| ECO Mode Efficiency | Up to 99% |
| Dimensions and Weight | |
| Dimensions (W x D x H) in mm Rack Mounted Arrangement | 430x450x85 |
| Weight (kg) | 11 |
| General | |
| Nosie at 1 m (dBA) | 55 |
| Operating Temperature (°C) | 0 ~ 50* |
| Relative Humidity (%RH) | 5 ~ 95, non-condensing |
| Altitude (m) | 3000m |
| General and safety requirements for UPS | IEC/EN 62040-1 |
| EMC requirements for UPS | IEC/EN 62040-2 |
| UPS classification according to IEC 62040-3 | VFI-SS-111 |
| T&C | |
| Warranty | 1 Year on UPS |
| Vertiv T&C | *Conditions apply (1) with ABS certi cation (2) Not Available in 30kVA |