The Liebert S600E is a fully-digital, highly reliable, double conversion UPS solution that delivers clean and consistent power. This highly efficient solution is ideal for various deployments, whether it is IT racks, network closets, automation control systems, and precision instruments to small-sized control rooms among other edge applications. Liebert S600E offers best-in-class efficiency of up to 92% over a wide range of load conditions, resulting in significant OPEX cost savings. S600D's integrated Smart Sleep technology in ECO mode provides a superlative efficiency of up to 98%. Features : • Rating: 20 kVA/kW • Model: S600E • Phase: 3 Phase IN / 1 Phase OUT • I/P Voltage: 415Vac • O/P Voltage: Three Phase 380/400/415 Vac • Output Power Factor: Unity (1) i.e. kVA=kW • Efficiency >92% with Inbuilt Transformer • Inbuilt Isolation Transformer: Protects UPS and load from high voltage fluctuations. • Early Warning of UPS System Status • Power-Factor Correction: Prevents noise, harmonics, and distortion from being passed on to connected loads or from being fed back to the utility. • Lightning and Surge Protection • Wide Input Voltage Window • Manages all the nine power problems including sagging, spikes, and fluctuations. • Built-in-power charger for fast charging reduces battery charging time. • Integrated SNMP for monitoring and Modbus function • Settable battery options • Graphical screen system LCD display provides user-friendly operating interface.
| Isolation Transformer | Inbuilt |
| System Parameter | |
| Model | S600E |
| Rating | 20KVA/20KW |
| Phases | 3 Phase IN - 3 Phase OUT |
| Technology | IGBT based Double conversion PWM based online UPS |
| Parallel Mode | 4 (N+1) |
| Isolation Transformer | At Input Side |
| Installation Mode | Tower |
| Input | |
| Rated Voltage | 400VAC 3-phase,4-wire |
| Volatge Range | Three phase 305VAC -498VAC at 100% load,180VAC -498VAC at 50% load |
| Rated Frequency | 50Hz/60Hz |
| Frequency Range | 40Hz ~ 70Hz |
| THDi | <5% |
| Power factor | 0.99 at full load |
| Output | |
| Rated Power | 20KVA/20KW |
| Voltage | Three Phase 380/400/415 Vac |
| Frequency synchronization range | Rated frequency±3Hz. Configurable range: ±0.5Hz ~ ±5Hz |
| Rated Power Factor | Unity |
| Crest Factor | 3:1 |
| Voltage harmonic distortion | < 2% (linear load) |
| Voltage Regulation | 1 % |
| Dynamic response recovery time | 40 ms |
| Isolation Transformer | Inbuilt at UPS output |
| Inverter Overload Capability the utility mode | At 25°C: 105% ~ 125%- 5min; 125% ~ 150%-1min; 150%- more than 200ms |
| Inverter Overload Capability the battery mode | At 25°C :105% ~125%-60~ 30 s; >125%- more than 200ms |
| Bypass | |
| Maintenance Bypass | Inbuilt |
| Seprate Bypass | Inbuilt |
| Static Bypass | Inbuilt |
| Efficiency | |
| ECO Mode | >98% |
| Online mode (AC-AC) | > 92% |
| Inverter Efficiency (DC-AC) | >94% |
| Battery | |
| Type | Sealed Maintenance Free Valve Regulated Lead Acid/ Lithium-ion Batteries |
| No’s of Batteries | 24(1), 32, 34, 36, 38, 40; 32 by default |
| Battery Fuse Disconnector | Inbuilt |
| Battery charging Capacity | 13A |
| Transfer Time | |
| Transfer Time - Mains - Battery | 0 ms |
| Transfer Time - Inverter- Bypass | Asynchronous transfer (default): ≤20ms / Synchronous transfer: ≤0ms |
| UPS Parallel Numbers | 4 |
| Noise | <65db |
| Panel Display Mode | Graphical LCD display - Gravity Sense |
| Ambient Conditions | |
| Operating Temperature | 0°C ~ 50°C(2) |
| Storage Temperature | 40°C ~ +70°C (battery excluded); -25°C ~ +55°C (battery included) |
| Relative Humidity | 5%RH ~ 95%RH, non-condensing |
| Altitude | ≤3000m; derating when higher than 3000m |
| Machanical Parameter | |
| W*D*H (mm) | 335 X 650 X 1300 |
| Weight (Kg) | 175 |
| Ventilation | Forced Air Cooled |
| Ingress Protection | IP20 |
| Color | Powder coated Black Texture finish |
| Cable Entry | Bottom |
| Network Management | |
| Smart RS232/USB | Supports Windows 2000/2003/XP/Vista/2008,Windows 7,Linux,unix and MAC |
| Web-page Monitoring ( SNMP) | Inbuilt for Web-based monitoring |
| Advanced SNMP(Remote Alarm management) | Optional “RDU SIC G2” card needs to be considered for remote power management, alarm management, email alerts,etc. |
| Management Software | Site Monitor |
| Modbus | Inbuilt Via Multifunction port |
| T&C | |
| Warranty | 1 Year on UPS |
| Vertiv T&C | (1) UPS power will derate to 70% of the total capacity / (2) UPS power will derate to 80% at 40deg, 70% at 50deg *conditions applyTechnical |